Documentation

Analogue Demultiplexer (B10)

Block name

B10_ANALOGUE_DEMULTIPLEXER

ST call

PROGRAM B10_TEST
VAR
INPUT:REAL;
SELECTOR:INT;
O1,O2: REAL;
FB: LIB.CORE.V1_0.B10_ANALOGUE_DEMULTIPLEXER;
END_VAR
FB(IN:=INPUT, SEL:=SELECTOR);
O1:=FB.OUT[1];
O2:=FB.OUT[2];
END_PROGRAM

Library

LIB\CORE

Version

V1.0

Description

The block implements a demultiplexer for REAL variables.

Inputs

Input Type Description Default value
IN REAL Input value 0
SEL INT Output selector 0
DEFAULT REAL Default value of all outputs 0

Outputs

Output Type Description
OUT REAL Output signal.

Function

The block implements a demultiplexer for REAL variables. Setting of SEL=1 means that IN is copied to the OUT[1] output, SEL=2 means that IN is copied to OUT[2], etc. All other outputs are set to the DEFAULT value. If SEL does not match any of the available outputs (SEL<1 or sel>16), all outputs are in the DEFAULT value.