Operating Hours (T32)

Operating hours counter

Block name

T32_OPERATING_HOURS

ST call

PROGRAM TEST_T32
VAR
BOOL1,BOOL2,BOOL3: BOOL;
TIME1,TIME2:TIME;
DT1: DT;
FB: LIB.HVAC.V1_0.T32_OPERATING_HOURS;
END_VAR
FB(BSET:= BOOL1, ENABLED:= BOOL2, IN:= BOOL3,TINIT:= TIME1, OUT=> TIME2, TSET=>DT1);
END_PROGRAM

Library

LIB\HVAC

Version

V1.0

Description

The block measures total activity time of a binary input, or cumulated operating time of the connected aggregate (pump, fan, boiler).

Inputs

Input Type Description Default value
BSET BOOL Rising edge sets the counter to TINIT False
ENABLE BOOL This input must be TRUE for the block to operate False
IN BOOL Activity input False
TINIT TIME “Starting” value after reset, usually 0 0

Outputs

Output Typ Description
OUT TIME Total time the IN input was in TRUE
TSET DT Date and time of last reset (rising edge on BSET) as UTC

Function

The block acts as a stopwatch. Time measuring start is activated by bringing the IN input to True, and stopped by bringing IN to False. The default state is set by a rising edge at bset, while the block writes the TINIT value to the OUT output rather than the cumulated time. This becomes the starting value for further cumulation. TSET records the rising edge time.

Application example

The variable PUMP1FB gives the pump operation signal. The cumulated time is recorded in T32 and of the total operation time exceeds PUMP_SERVICE_TIME, an alarm to call for service inspection is generated.