Modbus RTU, TCP/IP – wrong packets displayed in System status when communicating

To get rid of wrong packets, increase Timeout in the Modbus protocol parameters. Default is 70 ms, while some 3rd party devices may require up to 250 ... 300 ms. Upload solution to apply changes.