PLC Time (B99)

PC (PLC) Time

Block name

B99_PCTIMENODE

ST call

PROGRAM TEST B99
VAR
LINT1 : LINT; // CAS V SEKUNDáCH
SINT1,SINT2,SINT3 :SINT;
END_VAR
LINT1 := LIB.CORE.V1_0.B99_PCTIMENODE(LOCAL:=TRUE, SEC=>SINT1,MIN=>SINT2,HOUR=>SINT3);
END_PROGRAM

Library

LIB\CORE

Version

V1.0

Description

The block returns UTC or local time, together with iother time units.

Inputs

Input Type Description Default value
LOCAL BOOL Local or UTC time? (UTC = false, Local = true) True

Outputs

Output Type Description
=> LINT Time in s
MSEC INT Milliseconds (May not be supported for certain platforms)
SEC SINT Seconds
MIN SINT Minutes
HOUR SINT Hours
DAY SINT Days
WDAY SINT Day of week (0 = Sunday, 1 = Monday, ..., 6 = Saturday)
MON SINT Months
YEAR INT Years
DAYLIGHT BOOL daylight=true means that the Daylight saving time (DST) is active (only makes sense for local time)
REMAINDAY SINT Remaining days until end of the month (last day: remainday = 0)

Function

The block outputs the real time of the SoftPLC. The output => gives total time in seconds starting at 1.1.1970, 0:00, and the wday output indicates the day of week (0 = Sunday, 1 = Monday, ..., 6 = Saturday).

The parameter local specifies if the time to consider is UTC or local time (local=true means time of the PC or PLC-preset time zone).

Poznámka

For MiniPLC platform-based controllers, the msec output = 0.

Application example

The block is used for periodical launching of programs and events, such as meter reading (e.g. last day of the month at 23:00), or for general time/date based calculations.