Indicator of alarm states. The object displays status of an alarm block, and alarm can be acknowledged or reset here according to its state - see table below. An alarm block has five possible states:
State | Display indication | Description | Possible actions | alr_status variable value |
Normal | OK | Normal state, no alarm | - | 0 |
Alarm active | * | Active unacknowledged alarm | Acknowledge | 1280 |
Active acknowledged | * + tick | Alarm acknowledged, still active | - | 1792 |
Memory, acknowledged | -x | Acknowledged, inactive | Reset | 1536 |
Memory, unacknowledged | - | Inactive, unacknowledged | Reset | 1024 |
To keep full functionality, the object must be linked with blocks "Lib.Core.V1_1.BD56_SingleAlarmMemoryDelay" or "Lib.Core.V1_1.BD57_AlarmMemoryExt", variable alr_status
The "Alarm status" object properties are:
Display type -object type (use Alarm for displaying of the alarm status)
Display name for LCD - Text to be displayed on the terminal, followed by the actual alarm status text
Variable - Path to the variable which contains the alarm status ( .AlrStatus by default)
Alarm Acknowledge Text - Text to be displayed as a hint for alarm acknowledgement
Alarm Reset Text - Text to be displayed as a hint for alarm reset
Acknowledge Variable - Path to variable which is used to acknowledge alarm ( .MkoAckSw.In by default)
Reset Variable - Path to variable which is used to reset alarm (.MkoRstSw.In by default)
Alarm Status Variable - Path to variable which is used to read and write alarm status ( .AlrStatus by default)
Automated spaces - Adds a spaces between "Display Type" and other text properties (string format, unit, states...).
Display of analogue value.
The "Analog Indicator" object properties are:
Display type - object type (Analog Indicator)
Display name for LCD - Text to be displayed on the terminal, followed by value and units
Variable - Path to the variable attached to the object
Formatting string - Definition of the format of displayed value, the "#" characters represent positions related to the decimal point. If the number has more decimal spaces than set in formatting string, the value will be rounded. Zeros are not displayed instead of missing numbers infront of the decimal point. If the formatting string is set as "###,##" and the number is 99,12345, the result will be 99,12.
Unit - Physical unit of the displayed value, will be displayed after the value
Object to set analog value.
The "Analog Setter" object properties are:
Display type - object type (Analog Setter)
Display name for LCD - Text to be displayed on the terminal, followed by value and units
Variable - Path to the variable attached to the object
Formatting string - Definition of the format of displayed value, the "#" characters represent positions related to the decimal point. If the number has more decimal spaces than set in formatting string, the value will be rounded. Zeros are not displayed instead of missing numbers in front of the decimal point. If the formatting string is set as "###,##" and the number is 99,12345, the result will be 99,12.
Unit - Physical unit of the displayed value, will be displayed after the value
Min - Minimum value which can be set using Analog Setter
Max - Maximum value which can be set using Analog Setter
Step - Decrement or increment on clicking of the - or + button
Displays a predefined text according to a discrete numerical value.
The "Digital Indicator" object properties are:
Display type - object type (Digital Indicator)
Display name for LCD - Text to be displayed on the terminal, followed by a text from the Collection
Variable - Path to the variable attached to the object
States mapping - Editor which edits integer values and corresponding texts of the states
States mapping
In States mapping the states corresponding to variable values are mapped. The values are Integer or "True(1)/False(0)". The longest text is taken for the preview and other calculations.
Sets a predefined discrete numerical value according to a selected state text from the collection.
The "Digital Setter" object properties are:
Display type - object type (Digital Setter)
Display name for LCD - Text to be displayed on the terminal, followed by a text from the Collection
Variable - Path to the variable attached to the object
States mapping - Editor which edits integer values and corresponding texts of the states
States mapping
In States mapping the states corresponding to variable values are mapped. The values are Integer or "True(1)/False(0)". The longest text is taken for the preview and other calculations.
The "HMI Template" object inserts a predefined template into a text menu. If this is a PLC menu, it is possible to insert a HMI program template or function block template. If this is a terminal menu, it is possible to insert a HMI program template or function block template, or a complete PLC template. See more on general HMI templates in the Full mode help.
The "HMI Template" object properties are:
Display type - object type (HMI Template)
Display name for LCD - Text to be displayed on the LCD
Variable - Path to the function block / program / PLC which is attached to the object
HMI Template - Selected HMI template for the function block / program / PLC
The "Login" item creates a locked branch in the LCD menu. The password is a 4-digit PIN. If the unlocked path is left, it locks automatically after Timeout expires.
The "Login" object properties are:
Display type - object type (Login)
Display name for LCD - Text to be displayed on the LCD
PIN - A fixed 4-digit code to allow entering the locked menu branch
Timeout - if the unlocked branch is left, it locks again automatically after "Timeout" expires
Displays a fixed text. It is used mostly in the main screen (site name), naming of menu branches (Setpoints, Heating, AHUs, Lights, etc.), or to create a submenu with supplier/service contact data (such as web pages and phone number).
The "Static Text" object properties are:
Display type - object type (Static Text)
Display name for LCD - Text to be displayed on the LCD
The "System DateTime" displays the local PLC date and time. Editing can be enabled in the object properties.
The "System DateTime" object properties are:
Display type - object type (System DateTime)
A similar object, System Date Time Setter, is used to set the PLC date and time over the terminal.
The "TPG Bool" object displays and edits a "Lib.Hvac.V1_0.T17_Boolean_Scheduler" or "Lib.Hvac.V1_0.T17_Boolean_Scheduler_Base" block.
The "TPG Bool" object properties are:
Display type - object type (TPG Bool)
Display name for LCD - Text to be displayed on the LCD, before the time program actual value
Variable - Attached variable. For a "TPG Bool" object attach a "Lib.Hvac.V1_0.T17_Boolean_Scheduler" block, or "Lib.Hvac.V1_0.T17_Boolean_Scheduler_Base" block..
True Text - Text to be displayed of the TPG output is "True" (such as Day)
False Text - Text to be displayed of the TPG output is "False" (such as Night)
The "TPG Int" object displays and edits a "Lib.Hvac.V1_0.T19_Integer_Scheduler" or "Lib.Hvac.V1_1.T19_Integer_Scheduler_Base" block.
The "TPG Int" object properties are:
Display type - object type (TPG Bool)
Display name for LCD - Text to be displayed on the LCD, before the time program actual value
Variable - Attached variable. For a "TPG Int" object attach a "Lib.Hvac.V1_0.T19_Integer_Scheduler" or "Lib.Hvac.V1_1.T19_Integer_Scheduler_Base" object.
States mapping
In States mapping the states corresponding to variable values are mapped. The values are Integer or "True(1)/False(0)". The longest text is taken for the preview and other calculations.
The "TPG Real"object displays and edits a "Lib.Hvac.V1_0.T18_Real_Scheduler" or "Lib.Hvac.V1_0.T18_Real_Scheduler_Base" block.
The "TPG Real" object properties are:
Display type - object type (TPG Real)
Display name for LCD - Text to be displayed on the LCD, before the time program actual value
Variable - Attached variable. For a "TPG Real" object, attach a "Lib.Hvac.V1_0.T18_Real_Scheduler" or "Lib.Hvac.V1_0.T18_Real_Scheduler_Base" block.
Formatting string - format of the displayed value. If the number has more decimal spaces than set in formatting string, the value will be rounded. Zeros are not displayed instead of missing numbers infront of the decimal point. If the formatting string is set as "###,##" and the number is 99,12345, the result will be 99,12.
Min - Minimum value which can be set set using Analog Setter
Max - Maximum value which can be set set using Analog Setter
Step - Decrement or increment on clicking of the - or + button