BD56_SINGLEALARMMEMORYDELAY
PROGRAM TEST BD56
VAR
BOOL1,BOOL2,BOOL3,BOOL4,BOOL5 :BOOL;
TIME1 : TIME;
INT1:INT;
FB : LIB.CORE.V1_1.BD56_SINGLEALARMMEMORYDELAY;
END_VAR
FB(IN:=BOOL1,ACK1:=BOOL2,RESET1:=BOOL3,DELAY:=TIME1);
BOOL4 := FB.ACKNOWLEDGED;
BOOL5 := FB.MEMORY;
INT1 := FB.ALRSTATUS;
END_PROGRAM
LIB\CORE
V1.1
The block is an alarm memory which responds after a time delay only.
Input | Type | Description | Default value |
---|---|---|---|
IN | BOOL | Alarm input | False |
ACK1 or ACK2 | BOOL | Alarm acknowledge | False |
RESET1 or RESET2 | BOOL | Alarm memory reset | False |
DELAY | TIME | Alarm delay | 30s |
Output | Type | Description |
---|---|---|
ACKNOWLEDGED | BOOL | Indication that the alarm has been acknowledged |
MEMORY | BOOL | Alarm memory |
ALRSTATUS | INT | Alarm status |
The block is a memory block which keeps alarm status for display in SCADA or for interlocking of the controlled aggregates. After a rising edge on the in input the time delay is measured. If the input TRUE level lasts even after the delay time expires, the block goes into alarm, indicating alarm memory at the memory output. The alarm can be acknowledged either via SCADA or other client, or by bringing a rising edge to the ack input. Then, the acknowledged output goes to TRUE. After the alarm signal disappears (in goes to FALSE), the alarm can be reset by bringing a rising edge to the reset1 or reset2 inputs.
Values of alrstatus:
The alrstatus value may be a composition of more above mentioned indicators.
The alarm block is one of the most frequently used blocks in the HVAC control programs. It is used for safety interlock of pumps and fans, which are prevented from operation until their alarm blocks are reset manually over a HMI or SCADA (or by a general alarm reset button at the panel door).